SRM/3/TEMPRISINGALARM: OID [OID] temperature over high threshold .(EntityPhysicalIndex=[INTEGER1], BaseThresholdEntry_entPhysicalIndex=[INTEGER2], BaseThresholdEntry_hwBaseThresholdType=[INTEGER3], BaseThresholdEntry_hwBaseThresholdIndex=[INTEGER4], BaseTrapSeverity=[INTEGER5], BaseTrapProbableCause=[INTEGER6], BaseTrapEventType=[INTEGER7], EntPhysicalName=[OCTET], BaseThresholdValue=[INTEGER8], BaseThresholdUnit=[INTEGER9], BaseThresholdHighWarning=[INTEGER10], BaseThresholdHighCritical=[INTEGER11])
The temperature exceeded the upper threshold.
Alarm ID | Alarm Severity | Alarm Type |
---|---|---|
1.3.6.1.4.1.2011.5.25.129.2.2.1 |
Minor |
equipmentAlarm(5) |
Name | Meaning |
---|---|
OID |
Indicates the MIB object ID of the alarm. |
EntityPhysicalIndex |
Entity index. |
BaseThresholdEntry_entPhysicalIndex |
Index of the entity causing this temperature alarm. |
BaseThresholdEntry_hwBaseThresholdType |
Type of the detected entity (The value 1 indicates the temperature sensor of a certain type that is adopted by the S-switch.) |
BaseThresholdEntry_hwBaseThresholdIndex |
Index of the temperature sensor (The value begins from 1.) |
BaseTrapSeverity |
Severity code. |
BaseTrapProbableCause |
Error code. |
BaseTrapEventType |
Code of the event type. |
EntPhysicalName |
Entity name. |
BaseThresholdValue |
Current temperature. |
BaseThresholdUnit |
Unit of the temperature. |
BaseThresholdLowWarning |
Upper threshold of the temperature. |
BaseThresholdLowWarning |
Major upper threshold of the temperature. |
When the temperature exceeds the upper threshold, the switch may not work properly and packet loss may occur. Or more seriously, the system may not respond or reset abnormally.
The chassis is not ventilated well, which causes heat unable to be dissipated.
The ambient temperature is high.
There are not enough fans in the switch.
One or more fans in the switch have failed.