SRM_1.3.6.1.4.1.2011.5.25.129.2.2.3 hwTempFallingAlarm

Description

SRM/3/TEMPFALLINGALARM: OID [OID] temperature below minor threshold .(EntityPhysicalIndex=[INTEGER1], BaseThresholdEntry_entPhysicalIndex=[INTEGER2], BaseThresholdEntry_hwBaseThresholdType=[INTEGER3], BaseThresholdEntry_hwBaseThresholdIndex=[INTEGER4], BaseTrapSeverity=[INTEGER5], BaseTrapProbableCause=[INTEGER6], BaseTrapEventType=[INTEGER7], EntPhysicalName=[OCTET], BaseThresholdValue=[INTEGER8], BaseThresholdUnit=[INTEGER9], BaseThresholdLowCritical=[INTEGER10], BaseThresholdLowWarning=[INTEGER11])

This alarm was generated when the temperature was lower than the lower threshold.

Attribute

Alarm ID Alarm Severity Alarm Type
1.3.6.1.4.1.2011.5.25.129.2.2.3 Minor equipmentAlarm(5)

Parameters

Name Meaning
OID Indicates the MIB object ID of the alarm.
EntityPhysicalIndex Entity index.
BaseThresholdEntry_entPhysicalIndex Index of the entity causing this temperature alarm.
BaseThresholdEntry_hwBaseThresholdType Type of the detected entity (The value 1 indicates the temperature sensor of a certain type that is adopted by the S-switch.)
BaseThresholdEntry_hwBaseThresholdIndex Index of the temperature sensor (The value begins from 1.)
BaseTrapSeverity Severity code.
BaseTrapProbableCause Error code.
BaseTrapEventType Code of the event type.
EntPhysicalName Entity name.
BaseThresholdValue Current temperature.
BaseThresholdUnit Unit of the temperature.
BaseThresholdLowCritical Major lower threshold of the temperature.
BaseThresholdLowWarning Lower threshold of the temperature.

Impact on the System

After the temperature exceeds the lower threshold, the device may fail to work normally. That is, packet loss may occur or even more seriously, the device may be suspended or abnormally reset.

Possible Causes

1. The lower threshold of the temperature was too high.

2. The ambient temperature was too low.

Procedure

  1. Run the display temperature { all | slot slot-id } command to check whether the ambient temperature is too low.

    • If so, increase the ambient temperature by turning up the air-conditioner.
    • If not, go to step 2.

  2. Run the display temperature { all | slot slot-id } command to check whether the set lower threshold of the temperature is too high.

    • If so, set the lower threshold of the temperature to a proper value. It is recommended that you run the undo temperature threshold unit unit-id command to restore the lower threshold to the default value.
    • If not, the alarm handling ends.