No. |
Description |
---|---|
1 |
The grounding wire should not run parallel to or twist around the signal cable. |
2 |
Bury ground underground or arrange them indoors. Do not route ground cables overhead. |
3 |
Do not connect two cables together to extend the PGND cable, or add any switches or fuses. |
4 |
The PGND cable should be an alternating yellow and green plastic insulated one with a copper core. |
5 |
The neutral line of the AC power cable cannot be connected to the protective ground of transmission and communication equipment in the equipment room. |
6 |
A PGND cable should be as short as possible, with a length of no more than 45 m (147.64 ft). |