DEVM_1.3.6.1.4.1.2011.5.25.129.2.1.9 hwEntityInvalid-67634

Trap Buffer Description

Physical entity failed. (BaseTrapSeverity=[BaseTrapSeverity], BaseTrapProbableCause=[67634], BaseTrapEventType=[BaseTrapEventType], EntityPhysicalIndex=[EntityPhysicalIndex], EntPhysicalContainedIn=[EntContainedIn], EntPhysicalName=[EntPhysicalName], RelativeResource=[RelativeResource], ReasonDescription=The AC power supply module was faulty.)

Physical entity failed.

In VS mode, this trap is supported only by the admin VS.

Trap Attributes

Trap Attribute Description

Alarm or Event

Alarm

Trap Severity

Alert

Mnemonic Code

hwEntityInvalid

Trap OID

1.3.6.1.4.1.2011.5.25.129.2.1.9

MIB

HUAWEI-BASE-TRAP-MIB

Alarm ID

0x08130055

Alarm Name

hwEntityInvalid

Alarm Type

equipmentAlarm

Raise or Clear

Raise

Match trap

DEVM_1.3.6.1.4.1.2011.5.25.129.2.1.10 hwEntityResume-67634

Trap Buffer Parameters

Parameter Description

BaseTrapSeverity

To describe the level of trap.

ProbableCause

To describe the probable cause of trap.

BaseTrapEventType

To describe the type of trap.

EntityPhysicalIndex

The index of the physical entity.

EntContainedIn

The value of entPhysicalIndex for the physical entity.

EntPhysicalName

The textual name of the physical entity.

RelativeResource

This object may contain a key word to indicate the relative resource of an entity.

ReasonDescription

To describe the reason of trap in DisplayString style.

VB Parameters

VB OID VB Name VB Index

1.3.6.1.4.1.2011.5.25.129.1.1

hwBaseTrapSeverity

-

1.3.6.1.4.1.2011.5.25.129.1.2

hwBaseTrapProbableCause

-

1.3.6.1.4.1.2011.5.25.129.1.3

hwBaseTrapEventType

-

1.3.6.1.2.1.47.1.1.1.1.4

entPhysicalContainedIn

entPhysicalIndex

1.3.6.1.2.1.47.1.1.1.1.7

entPhysicalName

entPhysicalIndex

1.3.6.1.4.1.2011.5.25.129.1.4

hwBaseTrapRelativeResource

-

1.3.6.1.4.1.2011.5.25.129.1.5

hwBaseTrapReasonDescr

-

Impact on the System

The system's power supply function will not be affected, but the power supply reliability will be affected.

Possible Causes

The AC power supply module was faulty.

Procedure

1. Check whether the power supply module is well installed.

  • If so, go to Step 3.
  • If not, go to Step 2.

2. Re-install the power supply module and then check whether the alarm is cleared.

  • If so, go to Step 6.
  • If not, go to Step 4

3. Perform an active/standby switchover, and then check whether the alarm is cleared.

  • If so, go to Step 6.
  • If not, go to Step 4.

4. Replace the power supply module and check whether the alarm is cleared.

  • If so, go to Step 6.
  • If not, go to Step 5.

5. Collect trap, log, and configuration information, and contact technical support.

6. End.