DEVM_1.3.6.1.4.1.2011.5.25.129.2.2.1 hwTempRisingAlarm-70656

Trap Buffer Description

SRM_BASE/2/TEMPRISINGALARM: OID 1.3.6.1.4.1.2011.5.25.129.2.2.1 Temperature exceeded the upper prealarm limit. (EntityPhysicalIndex=[ULONG], EntityPhysicalIndex=[ULONG], BaseThresholdType=1, BaseThresholdEntityPhysicalIndex=[ULONG], BaseTrapSeverity=6, BaseTrapProbableCause=70656, BaseTrapEventType=6 EntPhysicalName=[STRING], BaseThresholdValue=[ULONG],, BaseThresholdUnit=2 HighWarning=[ULONG], HighCritical=[ULONG])

The temperature of a physical entity exceeded the upper limit.

In VS mode, this trap is supported only by the admin VS.

Trap Attributes

Trap Attribute Description

Alarm or Event

Alarm

Trap Severity

Alert

Mnemonic Code

hwTempRisingAlarm

Trap OID

1.3.6.1.4.1.2011.5.25.129.2.2.1

MIB

HUAWEI-BASE-TRAP-MIB

Alarm ID

0x081300a9

Alarm Name

hwTempRisingAlarm

Alarm Type

environmentalAlarm

Raise or Clear

Raise

Match trap

DEVM_1.3.6.1.4.1.2011.5.25.129.2.2.2 hwTempRisingResume-70656

Trap Buffer Parameters

Parameter Description

BaseTrapSeverity

Indicates the severity level of the trap reported to the NMS.

BaseTrapProbableCause

Indicates possible causes.

BaseTrapEventType

Indicates the type of the trap.

EntityPhysicalIndex

Indicates the physical index.

entPhysicalName

Indicates the name of the entity.

BaseThresholdValue

Indicates the actual value.

BaseThresholdUnit

Indicates the unit of the value (mV).

BaseThresholdHighWarning

Indicates the minor upper limit.

BaseThresholdHighCritical

Indicates the upper critical limit.

VB Parameters

VB OID VB Name VB Index

1.3.6.1.4.1.2011.5.25.129.1.1

hwBaseTrapSeverity

-

1.3.6.1.4.1.2011.5.25.129.1.2

hwBaseTrapProbableCause

-

1.3.6.1.4.1.2011.5.25.129.1.3

hwBaseTrapEventType

-

1.3.6.1.2.1.47.1.1.1.1.7

entPhysicalName

entPhysicalIndex

1.3.6.1.4.1.2011.5.25.129.1.6.1.3

hwBaseThresholdValue

entPhysicalIndex

hwBaseThresholdType

hwBaseThresholdIndex

1.3.6.1.4.1.2011.5.25.129.1.6.1.4

hwBaseThresholdUnit

entPhysicalIndex

hwBaseThresholdType

hwBaseThresholdIndex

1.3.6.1.4.1.2011.5.25.129.1.6.1.7

hwBaseThresholdHighWarning

entPhysicalIndex

hwBaseThresholdType

hwBaseThresholdIndex

1.3.6.1.4.1.2011.5.25.129.1.6.1.8

hwBaseThresholdHighCritical

entPhysicalIndex

hwBaseThresholdType

hwBaseThresholdIndex

Impact on the System

Services will not be affected

Possible Causes

Cause 1: The slot where no board is installed was not inserted with a filler panel.

Cause 2: The air filter was blocked.

Cause 3: The environmental temperature was too high.

Cause 4: The fan was faulty.

Cause 5: The temperature of the chip was too high.

Procedure

1. Run the display temperature slot slot-id command in the user view to view the temperature of each board.

2. Check whether a filler panel is inserted in the slot where no board is installed.

  • If so, go to Step 4.
  • If not, go to Step 3.

3. Insert filler panel in the slots where no board is installed and check whether the alarm is cleared.

  • If so, go to Step 9.
  • If not, go to Step 3.

4. Check whether the fan is faulty.

  • If so, go to Step 11.
  • If not, go to Step 5.

5. Replace the fan and check whether the alarm is cleared.

  • If so, go to Step 11.
  • If no, go to Step 6.

6. Check whether the air filter is blocked.

  • If so, go to Step 11.
  • If not, go to Step 7.

7. Clean the air filter and then check whether the alarm is cleared.

  • If so, go to Step 11.
  • If not, go to Step 8.

8. Check whether the environmental temperature is too high.

  • If so, go to Step 9.

9. If the environmental temperature is normal, the temperature of the chip must be too high. In such a case, no action is required. Then, go to Step 10.

10.Adjust the environmental temperature and then check whether the alarm is cleared.

  • If so, go to Step 11.
  • If not, go to Step 10.

10. Collect trap, log, and configuration information, and contact technical support.

11. End.