Assembling the Cabinet Stand
Procedure
- Adjust the height of the cabinet stand.
- Measure the distance between the concrete floor and surface of the ESD floor with a measuring tape, as shown in Figure 1.
Figure 1 Measuring the ESD floor height
- Adjust the height of the cabinet stand according to the height of the ESD floor. See callout 1 in Figure 2.
- Tighten the height locking bolts on both sides. Do not tighten the bolts completely; leave some space for leveling the cabinet stand. See callout 2 in Figure 2.
Figure 2 Tightening height locking bolts
- Assemble the cabinet stand, as shown in Figure 3.
Figure 3 Assembling the cabinet stand
- Adjust the depth of the cabinet stand according to the cabinet depth.
- Fasten the six M8x20 bolts on the expandable levels using the torque socket. See callout 1 in Figure 3.
- Secure the expandable levels on the stand with eight M8x20 bolts. Use the torque socket to fasten all the bolts with a torque of 13 N•m. See callout 2 in Figure 3.
- Fasten the six M8x20 bolts on the expandable levels using the torque socket with a torque of 13 N•m. See callout 1 in Figure 3.
- Check the stand with a level. See callout 3 in Figure 3.
- If the stand leans, loosen the height locking bolts and adjust the height of the stand until the stand is level.
- Fasten all the locking bolts with a torque of 45 N•m. See callout 4 in Figure 3.