Assembling the Cabinet Stand

Procedure

  1. Adjust the height of the cabinet stand.
    1. Measure the distance between the concrete floor and surface of the ESD floor with a measuring tape, as shown in Figure 1.

      Figure 1 Measuring the ESD floor height

    2. Adjust the height of the cabinet stand according to the height of the ESD floor. See callout 1 in Figure 2.
    3. Tighten the height locking bolts on both sides. Do not tighten the bolts completely; leave some space for leveling the cabinet stand. See callout 2 in Figure 2.

      Figure 2 Tightening height locking bolts

  2. Assemble the cabinet stand, as shown in Figure 3.

    Figure 3 Assembling the cabinet stand

    1. Adjust the depth of the cabinet stand according to the cabinet depth.
    2. Fasten the six M8x20 bolts on the expandable levels using the torque socket. See callout 1 in Figure 3.
    3. Secure the expandable levels on the stand with eight M8x20 bolts. Use the torque socket to fasten all the bolts with a torque of 13 N•m. See callout 2 in Figure 3.
    4. Fasten the six M8x20 bolts on the expandable levels using the torque socket with a torque of 13 N•m. See callout 1 in Figure 3.
    5. Check the stand with a level. See callout 3 in Figure 3.
    6. If the stand leans, loosen the height locking bolts and adjust the height of the stand until the stand is level.
    7. Fasten all the locking bolts with a torque of 45 N•m. See callout 4 in Figure 3.
Copyright © Huawei Technologies Co., Ltd.
Copyright © Huawei Technologies Co., Ltd.
< Previous topic Next topic >