The equipment room should receive stable and reliable DC power. Deploy the power equipment near the telecommunications equipment to make the DC feeder as short as possible. To reduce power consumption and installation cost, the loop voltage drop from the battery port to the equipment port should be less than 3.2 V.
Table 1 lists the specifications for the DC power supply.
Item |
Requirements |
---|---|
DC power capacity to support the surge current |
Greater than 1.5 times the rated current |
Regulated voltage precision |
If the AC input voltage is in the range of 85% to 110% of the rated value, and the load current is in the range of 5% to 100% of the rated value, the output voltage of the rectifier ranges from -46.0 V to -56.4 V, with the regulated voltage precision less than or equal to 1%. |
Overshoot amplitude of switch on/off |
Integral value of the DC output voltage ±5% |
Peak noise voltage |
≤200 mV |
Dynamic response |
The recovery time is less than 200 ms. The overshoot is in the range of the integral value of the DC output voltage ±5%. |