DEVM/1/hwEntityInvalid_active-67629

Message

DEVM/1/hwEntityInvalid_active: Physical entity failed. (BaseTrapSeverity=[BaseTrapSeverity], BaseTrapProbableCause=[67629], BaseTrapEventType=[BaseTrapEventType], EntityPhysicalIndex=[EntityPhysicalIndex], EntPhysicalContainedIn=[EntContainedIn], EntPhysicalName=[EntPhysicalName], RelativeResource=[RelativeResource], ReasonDescription=One of the internal switches on a power module was not closed.)

In VS mode, this log is supported only by the admin VS.

Description

Physical entity failed.

Parameters

Parameter Name Parameter Meaning

BaseTrapSeverity

To describe the level of trap.

ProbableCause

To describe the probable cause of trap.

BaseTrapEventType

To describe the type of trap.

EntityPhysicalIndex

The index of the physical entity.

EntContainedIn

The value of entPhysicalIndex for the physical entity.

EntPhysicalName

The textual name of the physical entity.

RelativeResource

This object may contain a key word to indicate the relative resource of an entity.

ReasonDescription

To describe the reason of trap in DisplayString style.

Possible Causes

One of the internal switches on a power module was not closed.

Procedure

1. Check whether the switches on the power panel are off.

  • If one or more switches are not off, go to Step 2.
  • If all switches are off, go to Step 3.

2. Turn off the switches and check whether the alarm is cleared.

  • If so, go to Step 6.
  • If not, go to Step 3.

3. Run the slave switchover command to perform an active/standby switchover.

Check whether the alarm is cleared.

  • If so, go to Step 6.
  • If not, go to Step 4.

4. Replace the power module. Power off the faulty power module before replacing it.

Then, check whether the alarm is cleared.

  • If so, go to Step 6.
  • If not, go to Step 5.

5. Collect trap, log, and configuration information, and contact technical support.

6. End.