Context
Grounding the switch helps protect it from lightning,
electromagnetic interference, and electrostatic discharge, and is
the prerequisite for a PoE switch to provide power for a PD.
The ground cable can be connected to a ground bar or a ground
point on the cabinet or rack. The following procedure uses the connection
to a ground point as an example.
The switch
must be grounded before it is powered on. This protects operators
from electric shock and avoids equipment damage caused by lightning,
electromagnetic interference, or electrostatic discharge.
If a cabinet or rack has a protective coating, remove
this coating from around the ground point to ensure a reliable connection.
Follow-up Procedure
After the ground cable is connected, verify that the electrical
resistance between the ground terminal and ground point is less than
0.1 ohm on a multimeter.