Requirements for Corrosive Gases

The room should be free from dusts and corrosive gases, such as SO2, H2S, and NH3. Table 1 lists the requirements for the corrosive gas concentration.
Table 1 Requirements for corrosive gas concentration

Chemical active material

Unit

Concentration

SO2

mg/m3

≤0.30

H2S

mg/m3

≤0.10

NOx

mg/m3

≤0.50

NH3

mg/m3

≤1.00

Cl2

mg/m3

≤0.10

HCl

mg/m3

≤0.10

HF

mg/m3

≤0.01

O3

mg/m3

≤0.05

Take the following measures to meet the requirements:
  • Avoid constructing the room near a place where the corrosive gas concentration is high, such as a chemical plant.
  • Ensure the air intake vent of the room is in the prevailing upwind direction from any pollution source.
  • Place batteries in different rooms.
  • A professional service should monitor the corrosive gas conditions regularly.