< Home

Requirements for ESD Prevention

The absolute value of electrostatic voltage must be less than 1000 V.

Take the following measures to meet this requirement:
  • Train operators about ESD prevention.
  • Keep the correct humidity level in the equipment room to reduce the impact of static electricity.
  • Lay out an ESD floor in equipment rooms.
  • Wear ESD shoes and clothing before entering equipment room.
  • Use ESD tools, such as wrist straps, tweezers, and pullers.
  • Ground all conductive materials in the room, including computer terminals. Use ESD worktables.
  • Keep non-ESD materials (such as common bags, foam, and rubber) at least 30 cm (11.81 in.) away from boards and ESD-sensitive components.