AC Power Distribution Guide

Do not install power cables when the power is on. This is to avoid injuries.

Figure 1 Schematic diagram of the AC power distribution

AC Power Supply System

For cable specifications, see "Hardware Description"-Equipment Cables-Power Cables.

Table 1 PDF circuit breaker specifications

Item

Description

Remarks

Circuit breaker of each channel

≥10 A

NOTICE:

The circuit breaker current must not be greater than the maximum derating current of the device.

For hierarchical power supplying protection, the current of the circuit breaker at the user side should be no less than 10 A.

Installing AC Power Cables

  1. Route AC power cables along the cable ladder and lay them on the chassis.
  2. Insert the AC power cable to the AC input port and secure it using the loose-proof pinch as shown in Figure 2. Connect the other end of the AC power cable to the PDF of the equipment room.
    Figure 2 Installing the AC power cable
  3. Use cable ties to bundle AC cables every 150 mm upwards from the bottom and fasten the cables to the cable tray.
  4. Attach permanent labels 20 mm from both ends of each AC power cable.

Instructions for Connecting the AC Power Cable to the Power Distribution Box

  1. Cut the PE ground wire (yellow-green wire) at the peeling place (wrap it with insulation tape to prevent leakage or short circuit), peel the L wire (brown wire) and N wire (blue wire) and crimp the OT terminal Or cold-pressed terminal (terminal type is selected according to actual conditions).

  2. Connect the L and N wires to the corresponding L and N input terminals of the power distribution box.

    When using 110V power supply (dual live wire power supply), L and N are connected to the two live wires (L) of the equipment room and connected to the PGND cable. At the same time, both L and N poles must be configured with circuit breakers.