Do not install power cables when the power is on. This is to avoid injuries.
For cable specifications, see "Hardware Description"-Equipment Cables-Power Cables.
Item |
Description |
Remarks |
---|---|---|
Circuit breaker of each channel |
≥10 A NOTICE:
The circuit breaker current must not be greater than the maximum derating current of the device. |
For hierarchical power supplying protection, the current of the circuit breaker at the user side should be no less than 10 A. |
Cut the PE ground wire (yellow-green wire) at the peeling place (wrap it with insulation tape to prevent leakage or short circuit), peel the L wire (brown wire) and N wire (blue wire) and crimp the OT terminal Or cold-pressed terminal (terminal type is selected according to actual conditions).
Connect the L and N wires to the corresponding L and N input terminals of the power distribution box.
When using 110V power supply (dual live wire power supply), L and N are connected to the two live wires (L) of the equipment room and connected to the PGND cable. At the same time, both L and N poles must be configured with circuit breakers.