DRIVER/1/TEMPOVERMINORFAIL

Message

DRIVER/1/TEMPOVERMINORFAIL: [BoardSlotID], i2c[i2c], address[address], channel[channel] temperature over minor threshold, temperature is [CurValue]C.

In VS mode, this log is supported only by the admin VS.

Description

The temperature exceeded the minor upper threshold and the current temperature was provided.

Parameters

Parameter Name Parameter Meaning

BoardSlotID

Slot ID of a board

i2c

I2C value

address

IP address

channel

Channel number

CurValue

Current temperature

Possible Causes

Cause 1: A filler panel was not inserted to the empty slot.

Cause 2: The fan did not function properly.

Cause 3: The air filter of the fan module was clogged.

Cause 4: The ambient temperature was high.

Cause 5: The module temperature was high.

Procedure

Cause 1: A filler panel was not inserted to the empty slot.

1. After a filler panel is inserted to the empty slot, run the display_temperature slot slot-id command to check whether the temperature of the slot restores to the normal range.

  • If the temperature restores to the normal range, go to Step 3.
  • If the temperature fails to restore to the normal range, go to Step 2.

2. Collect the alarm information, log information, and configuration information, and contact technical support engineers.

3. End.

Cause 2: The fan did not function properly.

1. Replace the fan, and run the display_temperature slot slot-id command to check whether the temperature of the slot restores to the normal range.

  • If the temperature restores to the normal range, go to Step 3.
  • If the temperature fails to restore to the normal range, go to Step 2.

2. Collect the alarm information, log information, and configuration information, and contact technical support engineers.

3. End.

Cause 3: The air filter of the fan module was clogged.

1. Clean the air filter of the fan, and run the display_temperature slot slot-id command to check whether the temperature of the slot restores to the normal range.

  • If the temperature restores to the normal range, go to Step 3.
  • If the temperature fails to restore to the normal range, go to Step 2.

2. Collect the alarm information, log information, and configuration information, and contact technical support engineers.

3. End.

Cause 4: The ambient temperature was high.

1. Adjust the ambient temperature, and run the display_temperature slot slot-id command to check whether the temperature of the slot restores to the normal range.

  • If the temperature restores to the normal range, go to Step 3.
  • If the temperature fails to restore to the normal range, go to Step 2.

2. Collect the alarm information, log information, and configuration information, and contact technical support engineers.

3. End.

Cause 5: The module temperature was high.

  • If the ambient temperature is in the normal range, it means that the module temperature is high.