DEVM/1/hwFanInvalid_active: The fan module failed. (EntityPhysicalIndex=[EntityPhysicalIndex], EntPhysicalIndex=[EntPhysicalIndex], EntPhysicalName=[EntPhysicalName], EntityTrapFaultID=139267, Reason=The 48V power supply of the fan module is faulty.)
In VS mode, this log is supported only by the admin VS.
Parameter Name | Parameter Meaning |
---|---|
EntityPhysicalIndex |
The index for this entry. |
EntPhysicalIndex |
The index for this entry. |
EntPhysicalName |
The textual name of the physical entity. |
EntityTrapFaultID |
To describe the fault id of trap. |
Reason |
Reason. |
1. Check whether the 48 V power supply for the boards in the other slots is normal.
Two 48V power modules in backup mode supply power to fans.
2. If so, replace the fan module.
3. If there is an alarm of abnormal 48 V power supply on another board, refer to the handling procedure in hwPowerInvalid_136960.
4. If the alarm persists, collect alarm information, log information and configuration information, and then contact technical support personnel.
5. End.