Configuring Fault Message Transmission Between Ethernet CFM and Its Bound Interface

This section describes how to configure fault message transmission between Ethernet CFM and its bound interface in the OAM management view. After the configuration is complete, the link detection results of Ethernet CFM can be associated with the interface status.

Context

On the network shown in Figure 1, Ethernet CFM is deployed between the PEs. If a fault occurs on the link between the PEs, a CE needs to detect the fault. Additionally, if a fault occurs between a PE and CE, the PE needs to notify the remote PE of the fault to ensure reliable service transmission. To meet the needs, deploy fault message transmission between Ethernet CFM and its associated interface on a PE. For example, deploy fault message transmission between Ethernet CFM and its associated interface on PE2. If Ethernet CFM detects a fault on the link between PE1 and PE2, the physical status of interface 2 associated with Ethernet CFM on PE2 goes down. This triggers CE2 to detect the fault. If interface 2 on PE2 goes down, Ethernet CFM associated with the interface fails. PE2 uses CFM packets to transmit fault messages to PE1.
Figure 1 Fault message transmission between Ethernet CFM and its associated interface

Pre-configuration Tasks

Before configuring fault message transmission between Ethernet CFM and its bound interface, configure basic CFM functions.

Procedure

  1. Run system-view

    The system view is displayed.

  2. Run oam-mgr

    The OAM management view is displayed.

  3. Configure the association depending on the usage scenario:

    Table 1 Configurations for fault message transmission between Ethernet CFM and its bound interface

    Scenario

    Configuration Solution 1

    Configuration Solution 2

    Deploying bidirectional fault message transmission between Ethernet CFM and its bound interface

    Run the oam-bind cfm md ma trigger if-down interface or oam-bind interface cfm md ma trigger if-down command to configure bidirectional fault message transmission between Ethernet CFM and its bound interface.

    You can also run both of the following commands used for unidirectional fault message transmission to configure bidirectional fault message transmission.

    Run the following commands in any order (each command configures fault message transmission in a single direction):

    Deploying unidirectional fault message transmission between Ethernet CFM and its bound interface

    Select either of the following commands based on the direction in which fault messages are transmitted:

    None

  4. Run commit

    The configuration is committed.

Copyright © Huawei Technologies Co., Ltd.
Copyright © Huawei Technologies Co., Ltd.
< Previous topic Next topic >