DEVM/1/hwChassisFail_active: The chassis failed partially. (EntityPhysicalIndex=[EntityPhysicalIndex], EntPhysicalIndex=[EntPhysicalIndex], EntPhysicalName=[EntPhysicalName], EntityTrapFaultID=131350, Reason=Device power is insufficient for user config power limit.
In VS mode, this log is supported only by the admin VS.
Parameter Name | Parameter Meaning |
---|---|
EntityPhysicalIndex |
Indicates the index of the physical entity. |
EntPhysicalIndex |
Indicates the index of the physical entity. |
EntPhysicalName |
Indicates the name of the physical entity, such as chassis. |
EntityTrapFaultID |
Indicates the error code. |
ReasonDescription |
Indicates the description of the cause of the trap. |
The power supply would be abnormal because power limit was configured insufficiently.
1. Confirm with the customer whether the specified power consumption limit can be reached.
2. Increase the power consumption to make it reach the specified upper limit. Then, check whether the alarm can be cleared.
3. Insert more PMs and make them work. Then, check whether the alarm is cleared.
4. Collect trap, log, and configuration information, and contact technical support.
5. End.